| Process current | - Measuring range: 4 ... 20 mA
- Accuracy: < 0.3% of measuring range
- Overload:max. 25 mA
|
| Process voltage | - Measuring range:0 ... 10 V
- Accuracy: < 0.3% of measuring range
- Overload:max. 25 V DC
|
| Potentiometer0 ... 100 % | - Measuring range:0 ... 500 Ω
- Accuracy: < 1% of measuring range
- Measuring range:0 ... 20 kΩ
|
| Resistance | - Measuring range:0 ... 2.5 kΩ
- Accuracy: < 1% of measuring range
- Measuring range:0 ... 5 kΩ
- Measuring range:0 ... 10 kΩ
- Measuring range:0 ... 25kΩ
- Measuring range:0 ... 50 kΩ
- Measuring range:0 ... 100kΩ
|
| NTC(R25=10K; β=3500) | - Measuring range:-60 ... 90 °C / -76 ... 194 °F
- Accuracy: <1% of measuring range
|
| NTC (44006) | - Measuring range:-60 ... 90 °C / -76 ... 194 °F
- Measuring range:0 ... 90 °C / 32 ... 194 °F
|
| Thermoelement Type J | - Measuring range:0 ... 150 °C / 32 ... 302 °F
- Accuracy: <0.5% of measuring range
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 450 °C / 32 ... 842 °F
- Measuring range:0 ... 600 °C / 32 ... 1112 °F
- Measuring range:0 ... 800 °C / 32 ... 1472 °F
- Measuring range:0 ... 1000 °C / 32 ... 1832 °F
- Measuring range:0 ... 1200 °C / 32 ... 2192 °F
|
| Thermoelement Type K | - Measuring range:0 ... 150 °C / 32 ... 302 °F
- Accuracy: <0.5 % of measuring range
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 450 °C / 32 ... 842 °F
- Measuring range:0 ... 600 °C / 32 ... 1112 °F
- Measuring range:0 ... 800 °C / 32 ... 1472 °F
- Measuring range:0 ... 1000 °C / 32 ... 1832 °F
- Measuring range:0 ... 1350 °C / 32 ... 2192 °F
|
| Thermoelement Type N | - Measuring range:0 ... 150 °C / 32 ... 302 °F
- Accuracy: <1 % of measuring range
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 450 °C / 32 ... 842 °F
- Measuring range:0 ... 600 °C / 32 ... 1112 °F
- Measuring range:0 ... 800 °C / 32 ... 1472 °F
- Measuring range:0 ... 1000 °C / 32 ... 1832 °F
- Measuring range:0 ... 1300 °C / 32 ... 2192 °F
|
| Thermoelement Type E | - Measuring range:0 ... 150 °C / 32 ... 302 °F
- Accuracy: <0.5 % of measuring range
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 450 °C / 32 ... 842 °F
- Measuring range:0 ... 600 °C / 32 ... 1112 °F
- Measuring range:0 ... 900 °C / 32 ... 1652 °F
|
| Thermoelement Type T | - Measuring range:0 ... 100 °C / 32 ... 212 °F
- Accuracy: <1 % of measuring range
- Measuring range:0 ... 200 °C / 32 ... 392 °F
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 400 °C / 32 ... 752 °F
|
| Thermoelement Type R | - Measuring range:0 ... 900 °C / 32 ... 1652 °F
- Accuracy: <2 % of measuring range
- Measuring range:0 ... 1200 °C / 32 ... 2192 °F
- Measuring range:0 ... 1500 °C / 32 ... 2732 °F
- Measuring range:0 ... 1750 °C / 32 ... 3182 °F
|
| Thermoelement Type S | - Measuring range:0 ... 900 °C / 32 ... 1652 °F
- Accuracy: <2 % of measuring range
- Measuring range:0 ... 1200 °C / 32 ... 2192 °F
- Measuring range:0 ... 1500 °C / 32 ... 2732 °F
- Measuring range:0 ... 1750 °C / 32 ... 3182 °F
|
| Pt100 (2- & 3-wire) | - Measuring range:-200 ... 200 °C / -328 ... 392 °F
- Accuracy: <0.5 % of measuring range
- Measuring range:-100 ... 100 °C / -148 ... 212 °F
- Measuring range:-50 ... 50 °C / -58 ... 122 °F
- Measuring range:0 ... 100 °C / 32 ... 212 °F
- Accuracy: <0.3% of measuring range
- Measuring range:0 ... 200 °C / 32 ... 392 °F
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 400 °C / 32 ... 752 °F
- Measuring range:0 ... 500 °C / 32 ... 932 °F
- Measuring range:0 ... 600 °C / 32 ... 1112 °F
- Measuring range:0 ... 700 °C / 32 ... 1292 °F
|
| Pt500 | - Measuring range:-150 ... 150 °C / -238 ... 302 °F
- Accuracy: <1 % of measuring range
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 630 °C / 32 ... 1166 °F
|
| Pt1000 | - Measuring range:-150 ... 150 °C / -238 ... 302°
- Accuracy: <1 % of measuring range
- Measuring range:0 ... 300 °C / 32 ... 572 °F
- Measuring range:0 ... 630 °C / 32 ... 1166 °F
|
| Ni100 | - Measuring range:-60 ... 180 °C / -76 ... 356 °F
- Accuracy: <1% of measuring range
|
| Ni1000 | - Measuring range:-60 ... 180 °C / -76 ... 356 °F
- Accuracy: <1% of measuring range
|
| Temperature drift | 150 ppm/°C |
| Response time | 300 ms ( 0 ... 99 % of measuring range) |
| Output | - Active: 4 ... 20 mA; max. load 400 Ω
- Passive: 4 ... 20 mA; max. 30 V loop voltage
- 0 ... 10 V ; max. load 1 kΩ
|
| Settings | internal buttons |
| Display | internal LED display |
| Power supply | 18 ... 265 V AC/DC / 45 ... 65 Hz |
| Power consumption | < 1.5 W |
| Connectable cable cross-section | 1 ... 2.5 mm² |
| Protection category | 2 |
| Isolation | 2300 Vrms (max 60 s) |
| Degree of protection | IP30 |
| Mounting | 35 mm DIN rail mounting |
| Operating conditions | 0 ... 50 °C / 32 ... 122 °F / non-condensing |
| Storage conditions | -20 ... 70 °C / -4 ... 158 °F / non-condensing |
| Heating-up time | ca. 15 min. |
| Dimensions | 106 x 108 x 22.5 mm / 4.2 x 4.3 x 0.9" |
| Weight | ca. 150 g / < 1 lb |